Some Lennox 80MGF and G24M Series furnaces use the EGC direct spark integrated ignition
control. The EGC controls and monitors the entire
sequence of operation. On a call for heat from the thermostat
the control monitors the combustion air blower
pressure switch.
The control will not begin the heating
cycle if the pressure switch is closed (by-passed). Once
the pressure switch is determined to be open, the combustion
air blower is energized. When the differential in pressure
across the pressure switch is great enough, the pressure
switch closes and a 15 second pre-purge period
begins. After the pre-purge period, the gas valve will open
and ignition (spark) will be attempted for 10 seconds. After
ignition, the control initiates a ten second flame stabilization
period. The flame stabilization period allows the
burners to heat up and the flame to stabilize. Once flame
is established, the control will constantly monitor the burner
flame using flame rectification. Flame failure response time is
0.8 seconds.
If the initial attempt for ignition fails, the sequence is repeated
up to five times. After the fifth trial, the control goes into
"Watchguard". During watchguard mode, the entire unit will
be de-energized for one hour. After one hour the control will
repeat the ignition sequence. Watchguard may be manually
reset by breaking and remaking thermostat demand.
NOTE−If flame is established beyond the 10 second flame
stabilization period then lost, the control resets for five more
ignition trials. The control can be reset five times during one
unsatisfied thermostat demand, providing a maximum
of 25 trials for ignition
|